Fujitsu ASU36CLX1 Service Manual

The Fujitsu ASU36CLX1 is a 36,000 BTU split-type air conditioning unit with inverter technology, R32 refrigerant, high energy efficiency rating, wireless remote control, auto-swing louvres, quiet operation, anti-mold filter, self-diagnosis function, and multiple operation modes (cooling, heating, dry, fan). Below are key sections for safety precautions, technical specifications, installation procedures, maintenance, troubleshooting, and repair guidelines.

1. Safety Precautions 2. Technical Specifications 3. Installation Procedures 4. Electrical Connections 5. Operation and Controls 6. Maintenance Procedures 7. Troubleshooting Guide 8. Parts Replacement 9. Error Codes 10. Wiring Diagrams 11. Refrigerant Handling

Safety Precautions

Before servicing, ensure proper safety measures are followed to prevent injury and equipment damage.

Hazard TypePrecaution
Electrical ShockDisconnect power before servicing; use insulated tools
RefrigerantWear protective gloves and goggles when handling R32
Heavy PartsUse proper lifting techniques; two-person lift for outdoor unit
Sharp EdgesWear cut-resistant gloves during disassembly
High PressureRelease pressure before opening refrigerant lines
Rotating PartsEnsure fan is stopped before working near blades

Technical Specifications

Installation Procedures

Proper installation ensures optimal performance and longevity.

  1. Select installation location: Ensure adequate clearance (min 50cm around units)
  2. Mount indoor unit: Use mounting plate and level for proper alignment
  3. Install outdoor unit: Use vibration-absorbing pads and secure mounting
  4. Connect refrigerant piping: Flare connections properly; apply torque specified
  5. Connect drain hose: Ensure proper slope for water drainage
  6. Vacuum and charge: Evacuate system to 500 microns; charge with specified R32 amount

WARNING! Only certified technicians should install and service this equipment.

Electrical Connections

Follow electrical codes and manufacturer specifications for all connections.

ConnectionSpecification
Power Supply208-230V, 60Hz, dedicated circuit with disconnect
Wire SizeMinimum 10 AWG copper wire
Circuit Breaker25A time-delay fuse or circuit breaker
GroundingProper equipment grounding required
CommunicationShielded cable between indoor and outdoor units

Operation and Controls

Remote control functions and operational modes.

Remote Control: POWER, MODE (Auto/Cool/Dry/Fan/Heat), TEMP ▲▼, FAN SPEED, SWING, TIMER, SLEEP, RESET.

Operation Modes: Auto mode selects cooling or heating based on room temperature. Cooling mode maintains set temperature. Heating mode provides warmth. Dry mode reduces humidity. Fan mode circulates air without cooling/heating.

Maintenance Procedures

Regular maintenance ensures efficiency and prevents breakdowns.

  1. Clean air filters: Remove and wash every 2 weeks; dry completely before reinstalling
  2. Clean outdoor coil: Use soft brush and coil cleaner; rinse with water
  3. Check drain pan: Ensure no blockage; clean if necessary
  4. Inspect electrical connections: Tighten loose terminals; check for corrosion
  5. Verify refrigerant charge: Check superheat and subcooling
  6. Lubricate fan motors: If required by manufacturer specifications

Troubleshooting Guide

SymptomPossible CauseCorrective Action
Unit not startingPower supply, remote batteriesCheck circuit breaker; replace remote batteries
Poor cooling/heatingDirty filters, low refrigerantClean filters; check refrigerant charge
Water leakageClogged drain, improper slopeClear drain line; adjust slope
Unusual noiseLoose parts, fan obstructionTighten mounting; clear fan area
Error code displayedSystem faultRefer to error code section

Parts Replacement

Authorized parts and replacement procedures.

  1. Compressor: Requires recovery of refrigerant; follow specific replacement procedure
  2. Fan motor: Disconnect power; remove fan blade; replace motor
  3. PCB: Note wiring connections; transfer settings from old board
  4. Thermistor: Check resistance values; replace if out of specification
  5. Capacitor: Discharge before handling; match microfarad rating

Error Codes

CodeDescriptionAction
E1Room temp sensor faultCheck thermistor resistance
E2Pipe temp sensor faultCheck pipe thermistor
E3Pressure sensor faultCheck pressure sensor circuit
E4Communication errorCheck wiring between units
E5Inverter compressor faultCheck compressor and driver

Wiring Diagrams

Complete electrical schematics for indoor and outdoor units.

Indoor Unit: Power input, fan motor, control board, thermistors, display PCB, remote sensor.

Outdoor Unit: Compressor, fan motor, 4-way valve, pressure sensors, inverter board, contactors.

Inter-unit: Communication wiring between indoor and outdoor control boards.

Refrigerant Handling

Proper procedures for R32 refrigerant management.

  1. Recovery: Use approved recovery machine; recover to recovery cylinder
  2. Charging: Weigh in correct amount; liquid charge into high side
  3. Leak testing: Use electronic leak detector; check all connections
  4. Pressure testing: Use dry nitrogen; do not exceed rated pressure
  5. Evacuation: Achieve 500 microns vacuum; hold for 15 minutes

CAUTION! R32 is mildly flammable; no smoking or open flames during service.