Fujitsu ASU18RLF Installation Manual
The Fujitsu ASU18RLF is a high-efficiency split-type air conditioning unit with 18,000 BTU cooling capacity, R-410A refrigerant, inverter technology for energy savings, wireless remote control, auto-swing louvres, sleep mode, timer functions, and multiple fan speeds. Designed for residential and light commercial use with easy installation and maintenance features. Below are key sections for safety, installation procedures, electrical connections, commissioning, and troubleshooting.
Safety Precautions
Always follow safety guidelines to prevent injury and equipment damage.
| Warning Type | Precaution |
| Electrical Safety | Disconnect power before installation or maintenance |
| Refrigerant Handling | Use proper PPE when working with R-410A |
| Lifting Safety | Use proper lifting equipment for heavy components |
| Fire Prevention | Keep flammable materials away from unit |
| Installation Location | Ensure adequate clearance and ventilation |
Unit Specifications
- Model: ASU18RLF
- Cooling Capacity: 18,000 BTU/h
- Power Supply: 208-230V, 60Hz
- Refrigerant: R-410A
- Operating Range: Cooling: 14°F to 115°F
- Indoor Unit Dimensions: 31.5" x 11.8" x 8.7"
- Outdoor Unit Dimensions: 31.9" x 23.6" x 13.8"
- Max Piping Length: 82 feet
- Max Height Difference: 49 feet
Installation Tools Required
Essential tools for proper installation:
- Flaring tool set
- Torque wrench
- Vacuum pump
- Manifold gauge set
- Pipe cutter
- Leak detector
- Multimeter
- Level
- Drill with hole saw
NOTE: Use only tools designed for R-410A refrigerant systems.
Indoor Unit Installation
Proper indoor unit placement ensures optimal performance.
- Select location: Minimum 7 feet from floor, away from heat sources
- Mount mounting plate: Use level to ensure proper alignment
- Create wall opening: 2.5-inch diameter hole for piping
- Route piping and cables: Through wall opening to outdoor unit
- Hang indoor unit: Secure onto mounting plate
WARNING! Ensure wall can support unit weight (approx. 20 lbs).
Outdoor Unit Installation
Outdoor unit requires stable foundation and proper clearance.
- Select location: Minimum 12 inches clearance on all sides
- Prepare foundation: Concrete pad or vibration-absorbing pads
- Position unit: Ensure level installation
- Secure unit: Use anchor bolts if required
- Connect piping: Follow refrigerant piping guidelines
CAUTION! Protect unit from direct sunlight and snow accumulation.
Refrigerant Piping
Proper piping installation is critical for system performance.
| Pipe Size | Indoor Unit | Outdoor Unit |
| Liquid Line | 1/4 inch | 1/4 inch |
| Gas Line | 1/2 inch | 1/2 inch |
- Cut pipes to required length
- Deburr and clean pipe ends
- Flare connections: 45-degree angle, no scratches
- Apply refrigerant oil to flare nuts
- Connect pipes with proper torque
Electrical Connections
Follow electrical codes and manufacturer specifications.
- Disconnect all power sources
- Connect indoor unit: L1, L2, Ground
- Connect outdoor unit: L1, L2, Ground
- Connect communication cable between units
- Secure all connections with proper terminals
WARNING! Use copper conductors only. Follow local electrical codes.
Drainage System
Proper drainage prevents water damage and ensures efficient operation.
- Connect drain hose to indoor unit
- Route hose with downward slope (minimum 1/4 inch per foot)
- Secure connections with hose clamps
- Test drainage with water
- Insulate drain line in unconditioned spaces
Vacuum and Leak Testing
Essential steps to ensure system integrity.
- Connect vacuum pump to service ports
- Evacuate system to 500 microns or less
- Hold vacuum for 15 minutes (no rise)
- Charge with nitrogen for pressure test (550 PSI)
- Check all connections with leak detector
- Release nitrogen and final vacuum
Commissioning
Final steps to activate and test the system.
- Release refrigerant by opening service valves
- Check refrigerant charge (weigh-in method)
- Power on system
- Test cooling operation
- Verify remote control functions
- Check temperature differential (14-22°F)
- Record installation data
Troubleshooting
| Symptom | Possible Cause | Corrective Action |
| Unit not starting | Power supply issue | Check circuit breaker and wiring connections |
| Poor cooling | Low refrigerant | Check for leaks and proper charge |
| Water leakage | Clogged drain | Clear drain line and check slope |
| Unusual noise | Loose parts | Tighten all fasteners and check fan |
| Error codes | Sensor failure | Check sensors and control board |
Service Contact: Fujitsu Technical Support: 1-800-831-8821
Warranty: 7-year compressor, 5-year parts warranty
Fujitsu ASU18RLF Installation Manual © - All Rights Reserved 2025