The Fuji Pressure Transmitter is a precision instrument designed for accurate pressure measurement and transmission in industrial applications. It features high accuracy, robust construction, multiple output signals (4-20mA, HART protocol), various pressure ranges, temperature compensation, IP67 protection rating, and easy installation. Below are key sections for safety, features, installation, setup, operation, and troubleshooting.
Key components: Pressure sensor module, Electronics housing, Process connection, Cable gland, Display unit (optional), Configuration buttons.
| Feature | Description |
|---|---|
| Pressure Range | 0-100 psi to 0-5000 psi depending on model |
| Output Signal | 4-20mA two-wire with HART protocol |
| Accuracy | ±0.1% of span |
| Process Connection | 1/2" NPT or G1/2 thread |
| Electrical Connection | M20 x 1.5 cable gland |
| Display | LCD with backlight (optional) |
| Configuration | Local buttons or HART communicator |
| Material | 316L stainless steel wetted parts |
| Protection Rating | IP67 for dust and water resistance |
| Temperature Range | -40°C to 85°C (-40°F to 185°F) |
Unpack and inspect contents. Ensure proper mounting location.
WARNING! Do not apply pressure beyond specified range. Ensure process media is compatible with wetted materials.
Power on transmitter; configure basic parameters.
CAUTION! Ensure process isolation before performing maintenance. Use proper personal protective equipment.
Access configuration via local buttons or HART communicator.
Local Configuration: Use membrane buttons on housing for zero, span, damping, units.
HART Configuration: Connect HART communicator for advanced settings including linearization, characterization, alarm settings, and diagnostics.
Basic Settings: Zero adjustment, Span calibration, Damping (0.1-32 seconds), Engineering units selection, Output characterization.
Process connection: Threaded connection to process line. Electrical: Two-wire loop connection.
Tip: Use shielded cable and proper grounding for noise immunity.
Supports zero, span, and full calibration procedures.
WARNING! Use certified calibration equipment. Ensure proper pressure source isolation.
Diagnostics: Built-in self-test and diagnostics via HART. Configuration protection: Password protection for critical settings. Data logging: Optional data logging capability.
Depressurize and isolate before cleaning. Use isopropyl alcohol for electronics cleaning. Use appropriate solvent for process connection cleaning.
CAUTION! Do not use abrasive cleaners. Ensure complete drying before reconnection.
CE Compliant: Meets European Union requirements. ATEX: Certified for hazardous areas (specific models). SIL: Safety Integrity Level certification available. RoHS: Compliant with restriction of hazardous substances. For technical support, visit www.fujielectric.com or contact +81-3-5435-7200.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| No output signal | Power supply/wiring | Check power supply voltage; verify wiring connections; check fuse. |
| Erratic readings | Process conditions/wiring | Check for pulsations; verify proper grounding; inspect cable shielding. |
| Zero drift | Temperature effects/aging | Perform zero calibration; check ambient temperature; verify mounting stress. |
| Span error | Calibration/reference | Recalibrate span; verify reference standard accuracy; check for leaks. |
| HART communication failure | Resistor/configuration | Verify 250 ohm resistor; check communicator configuration; inspect connections. |
Reset: Use reset function in configuration menu to restore factory settings.
Service: +81-3-5435-7200; www.fujielectric.com