The Fuji Inverter Frenic 5000G11 is a high-performance AC drive designed for industrial applications, featuring advanced control algorithms, multiple operation modes, comprehensive protection functions, and user-friendly programming. Suitable for various motor control applications with voltage ranges from 200V to 480V and power capacities up to 630kW. Below are key sections for safety, features, installation, setup, operation, and troubleshooting.
Key components: Digital operator, Control terminals, Main circuit terminals, Cooling fan, Heat sink.
| Feature | Description |
|---|---|
| Control method | Sine wave PWM control |
| Frequency range | 0.1 to 400Hz |
| Input voltage | 200-240V ±10% (1-phase), 380-480V ±10% (3-phase) |
| Control modes | V/F control, Vector control |
| Digital operator | LCD display with keypad for parameter setting |
| Communication | RS-485, Modbus protocol |
| Protection functions | Overcurrent, Overvoltage, Undervoltage, Overheat |
| Braking options | Regenerative braking, DC injection braking |
| Accel/decel time | 0.1 to 3600 seconds |
| Multi-function inputs | 7 programmable digital inputs |
Unpack and inspect contents. Mount in suitable enclosure.
WARNING! High voltage present - disconnect power before installation. Ensure proper ventilation clearance.
Power on inverter; initialize parameters.
CAUTION! Verify motor parameters before operation to prevent damage.
Access parameters via digital operator. Front Panel: RUN, STOP/RESET, PROGRAM/ENTER, UP/DOWN arrows.
Digital Operator: LCD display, Function keys, Navigation keys, Frequency potentiometer.
Basic Parameters: F00 (Frequency reference), F01 (Operation method), F02 (V/F pattern), F03 (Maximum frequency), F04 (Minimum frequency), F05 (Rated voltage), F06 (Base frequency), F07 (Acceleration time), F08 (Deceleration time). Advanced Parameters: H00 (Motor selection), H01 (Motor capacity), H02 (Number of poles), H03 (Rated current).
Main circuit: Power input R/S/T, Motor output U/V/W. Control terminals: Forward/Reverse, Multi-speed, Analog input, Relay output.
Tip: Use shielded cables for control wiring to prevent noise interference.
Supports multiple operation modes for various applications.
WARNING! Do not operate without proper motor connection. Verify rotation direction.
Overcurrent protection (OC), Overvoltage protection (OV), Undervoltage protection (UV), Overheat protection (OH), Motor overload protection (OL), Ground fault protection (GF).
Regular inspection: Check for abnormal noise/vibration, loose terminals, dust accumulation. Cooling: Ensure ventilation paths are clear. Replacement: Cooling fan (every 3-5 years), DC bus capacitors (every 5-7 years).
CAUTION! Disconnect power before maintenance. Do not touch terminals while powered.
CE compliant: Meets European EMC and low voltage directives. UL/cUL listed: Complies with North American safety standards. RoHS compliant: Free of hazardous substances. For technical support, contact Fuji Electric or authorized distributor. Copyright © Fuji Electric Co., Ltd.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| No display | Power supply | Check input voltage; verify control power connection. |
| Motor doesn't run | Wiring/parameters | Check motor connections; verify run command and frequency reference. |
| Overcurrent fault | Load/motor | Reduce load; check for motor ground fault; extend acceleration time. |
| Overvoltage fault | Regeneration | Extend deceleration time; install braking resistor if needed. |
| Overheat fault | Ventilation | Clean air filter; ensure ambient temperature within limits. |
Reset: Press STOP/RESET to clear faults after addressing cause.
Service: Contact authorized Fuji Electric service center for repairs.